Toote toon ja tegelik värvus võivad erineda pildil kujutatust, kuna pildid on illustratiivse iseloomuga. Samuti on toote kirjeldus üldine ega pruugi sisaldada kõiki toote omadusi.
MULTIFUNCTIONAL COUNTER FOR ELECTRICAL INSTALLATIONS UT-595 UNI-T
2011719 LEC-MIE0165
5901436796770
Tarneaeg 6-10 t.p.
Kõik toote kohta
UT-595 is a multi-function meter designed for measuring by electricians in electrical installations.
The device is also a comprehensive electrical installation safety tester.
With the UT-595, you can measure insulation resistance, fault circuit resistance with and without tripping RCD, line resistance, continuity of protective and potential conductors, tripping current and RCD tripping time, voltage value AC and phase sequence display.
Attention!
In order to correctly measure the insulation resistance value, it is necessary to apply a high voltage.
During the measurement, you must be extremely careful and strictly follow the recommendations given in the device's instructions.
| Resistance measurement : | Test voltage 250 V : 0.05 MΩ ... 250 MΩ Test voltage 500 V : 0.05 MΩ ... 500 MΩ Test voltage 1000 V : 0.05 MΩ ... 1000 MΩ |
| Measurement accuracy : | 0.05 MΩ ... 1000 MΩ ± (5% + 5) |
| Open circuit voltage : | Test voltage ± 10% |
| Test current intensity : | 0.9 mA ... 1.1 mA |
| Short-circuit current intensity : | < 1.8 mA |
| AC voltage measurement : | 0 V ... 440 V ± (2% + 3) @ 1 V |
| DC voltage measurement : | 0 V ... ± 440 V ± (2% + 3) @ 1 V |
| Low resistance measurement : | 0.01 Ω ... 200 Ω ± (2% + 5) |
| Frequency measurement : | 20 Hz ... 100 Hz - for comparison purposes only |
| RCD test of residual current switches : | Operating voltage: 220V ± 10% Test current: 10mA / 30mA / 100mA / 300mA / 500mA Shutdown time intervals: 0 ... 2000 ms ± (5% + 5) @ 1/2 x rated current value 0 ... 500 ms ± (5% + 5) @ 1 x rated current value, RCD selective 0 ... 500 ms ± (5% + 5) @ 2 x nominal current value, RCD selective 0 ... 300 ms ± (5% + 5) @ 1 x nominal current value 0 ... 300 ms ± (5% + 5) @ 2 x rated current value 0 ... 40 ms ± (5% + 5) @ 5 x rated current value |
| Measuring the tripping current in the RCD : | Rising current test 10 mA / 30 mA / 100 mA / 300 mA / 500 mA ± 10% |
| Circuit breaker RCD test : | ✔ |
| Phase sequence test : | 100 V ... 440 V / 45 Hz ... 65 Hz |
| Continuity measurement of protective and compensating cables : | 0 Ω ... 199 Ω ± (2% + 5) Measuring current > 20 mA @ 0 ... 2 Ω |
| Line (LN) impedance measurement : | 0.05 Ω ... 1.99 Ω ± (5% + 5) 2 Ω ... 19.99 Ω ± (5% + 5) 20 Ω ... 2000 Ω ± (5% + 5) Measuring current: 20 A / 20 ms Future short-circuit current measurement range: 0 ... 26 kA |
| Short-circuit loop resistance measurement (L-PE) : | 0.05 Ω ... 1.99 Ω ± (5% + 5) 2 Ω ... 19.99 Ω ± (5% + 5) 20 Ω ... 2000 Ω ± (5% + 5) Measuring current: 20 A / 20 ms Future short-circuit current measurement range: 0 ... 26 kA |
| Automatic change of measuring scale : | ✔ |
| RS-232 : | - |
| USB : | - |
| Main features : | Warning about using high voltage during measurement, Phase 0° / 180° switch during RCD test, Automatic identification of AC/DC voltage, Reset zero function for low resistance measurement, Large, readable LCD display with illumination, Buzzer, Automatic shutdown, Low battery indicator , Aesthetic and solid production |
| Working temperature : | 0 °C ... 40 °C |
| Permissible relative humidity of the environment : | ≤ 85% (no condensation) |
| Meals : | 8 x 1.5V batteries, AA/LR6/FR6 type - included |
| Weight : | 1.1 kg |
| Dimensions : | 210 x 175 x 90 mm |
| Manufacturer / Brand : | UNI-T |
| Warranty : | 2 years |